Empty cart
Title Page
Login
Search 
 Control Web 8
 Drivers for Control Web
 DataLab
 DataCam
 DataLight
 For schools
 Other software
 Control Web - previous versions
 Services
DataLab EIB
 

DataLab EIB

Isolated interface USB/EIB

Code:DL-EIB
Price for system integrators (excl. VAT): 279 EUR
List price (excl. VAT): 310 EUR
Manufacturer:Moravian Instruments
 
TOTAL
Dealer Price (excl. VAT):
Total Price (excl. VAT):
*) Estimated availability varies depending on product options. Estimated availability does not include time of shipping and it is not obligatory.

DataLab IF/EIB Driver for Control Web
USB interface for connecting Control Web system device driver to EIB

CPU module for DataLab IF/EIB

  • System processor unit DataLab

  • 1 slot for the EIB I/O module

  • USB connection

  • Optional assembly on DIN bar

The unit is delivered only as a whole with the interface module DL-IF/EIB.

Dimensions

Indication of terminals

I/O modules

It is possible to mount the unit with one DL-IF/EIB I/O module. The module is connected to the CPU board through a connector. After mounting of the upper cover the module is mechanically fixed in its position.

Other modules of the DataLab system cannot be connected to this unit.

Handling of the I/O module

The unit is delivered mounted, including the connected DL-IF/EIB module. Since the unit does not make it possible to connect another module, it is not necessary to handle the I/O module in another manner.

Removing the module

Access to the module is gained after removing the upper cover of the unit. Lift the side with the connecting connector upwards by about 2 mm and remove the module by drawing from the CPU board.

Insertion of the module

Insert the module into the connector of the selected slot of the CPU board. After end-to-end insertion the edge of the module board fits behind the edge of the box. After mounting of the upper cover the module is mechanically fixed in its position.


Ordering codes

DataLab IF/EIB Interface USB/EIB (DL-CPM/EIB + DL-IF/EIB) on DIN bar
DataLab IF/EIB S Interface USB/EIB (DL-CPM/EIB + DL-IF/EIB) desktop variant

EIB interface module

  • System module DataLab

  • Independent supply of the EIB and USB part

  • Galvanic separation of the EIB and USB part

  • Throughput terminal board for easy connection

  • Indication of failure status

The module is delivered only as a whole with the processor module.

For connection of conductors the connector terminal board is used. This solution simplifies connection of signals and commissioning of control applications.

The DL-IF/EIB module contains a galvanically separated interface for the EIB busbar resolved by means of ASIC Siemens TP-UART. The module displays the hardware status by means of LED indicators.

Indication and meaning of terminals and LED

A 4.1

EIB +

A 4.2

EIB –

A 5.1

EIB +

A 5.2

EIB –

           
 
transmission into EIB (negated)
receipt from EIP
indication of RESET of the interface
under-voltage in the EIB network
exceeded chip temperature ON
 

Parameters of the module

The parameters of the module fulfil conditions for EIB devices connected to the TP medium.

EIB Uin DC 30 V (21 V–32 V)
EIB Imax. 1,6 mA


Ordering codes

DataLab IF/EIB Interface USB/EIB (DL-CPM/EIB + DL-IF/EIB) on DIN bar
DataLab IF/EIB S Interface USB/EIB (DL-CPM/EIB + DL-IF/EIB) desktop variant